|
Most
Frequently Asked Questions
- What are the
differences between electrical metallic tubing (EMT), rigid steel conduit
(RSC), and intermediate metal conduit (IMC)? Answer
- What National
Electrical Code® (NEC®) Articles cover IMC, RSC, and EMT? Answer
- What Standards
apply to steel conduit/tubing? Answer
- Can RSC, IMC
and EMT be direct-buried? Answer
- Can steel raceways be installed underground as a watertight system? Answer
- Can RMC, IMC and EMT be installed in concrete? Answer
- Do RSC, IMC
and EMT comply with the requirements of NFPA 130? Answer
- What is the
coefficient of expansion for steel conduit/EMT and why is this significant?
Answer
- What are the
metric designators for steel conduit/EMT? Answer
- What is the
fire rating of steel conduit/EMT? Answer
- Can IMC be used
as a service mast? Answer
- Does IMC provide
as much physical protection as rigid? Answer
- How do you thread
IMC? Answer
- What type of
threads are cut on RSC and IMC? Answer
- How can field-cut
threads be protected against corrosion? Answer
- Does RSC conform
to IEC standards? Answer
- Is RSC the same
as schedule 40 pipe? Answer
- Can EMT be used
over 600 volts? Answer
- Can steel conduit/tubing
be used as equipment grounding conductors or do you have to use a supplementary
conductor? Answer
- Does steel conduit/tubing
shield against electromagnetic interference (EMI)? Answer
- What are the
advantages of using steel conduit/tubing? Answer
- Can EMT be used
on roof-tops? Answer
- Are special
EMT fittings required for use in wet locations? Answer
- What is the
recycled content of steel conduit/tubing? Can I get LEED points for
using these products in my project? Answer
- Need more information?
Answer
|
2. Raceway
Articles were renumbered in the 2002 NEC®.
The following list shows the Article numbers that apply to IMC, RSC,
and EMT, followed by the former Article number in parentheses.
IMC NEC®
Article 342 (345)
RMC NEC®
Article 344 (346) Article 344 covers Rigid Metal Conduit (RMC), including
rigid steel conduit (RSC).
EMT NEC®
Article 358 (348)
Back
to Questions
|
|
3.
The following standards cover steel conduit/tubing. The American
Society for Testing Materials (ASTM) does not publish a standard
whose scope specifically covers steel electrical conduit and couplings.
Therefore, ASTM specifications do not apply to metal conduit for
use as a metal raceway for the installation of wires and cables in
accordance with the National Electrical Code®.
Electrical
Metallic Tubing (EMT) is Listed to Standard for Electrical Metallic
Tubing - Steel, UL 797 and produced to American National Standards
Institute - ANSI C80.3
Rigid
Steel Conduit - Steel (RSC) is Listed to Standard for Electrical
Rigid Metal Conduit - Steel, UL 6 and produced to American National
Standards Institute - ANSI C80.1
Intermediate Metal Conduit - Steel (IMC) is Listed to Standard
for Electrical Intermediate Metal Conduit - Steel, UL 1242 and produced
to American National Standards Institute - ANSI C80.6.
Additional
information on the titles and designations of standards or requirements
that have been used for the investigation of products in a specific
category can be found in the Underwriters Laboratories Inc.®,
General Information for Electrical Equipment Directory. The
UL product category for EMT is FJMX, for RSC is DYIX, and for IMC
is DYBY.
The
Federal government, in an effort to reduce costs, has undertaken
a process of identifying non-government and industry wide practices
that have been accepted previously by the Department of Defense under
the Single Process Initiative (SPI) for use in lieu of a specific
military or Federal Specification or standard. This process reduces
the burden of the government to product and maintain separate standards.
To this end WW-C-581 standards which covered both Rigid Steel Conduit
and Intermediate Metal Conduit, were cancelled and replaced by:
WW-C-581
Class 1 Type A with Standard for Electrical Rigid Metal Conduit -
Steel, UL 6
WW-C-581
Class 2 Type A with Standard for Electrical Intermediate Metal Conduit
-Steel, UL 1242
Back to Questions
|
|
4.
The 2005 National Electrical Code (NEC) allows the
direct burial of all three products as noted in their respective
Articles:
RSC
Section 344.10 (B) Corrosion Environments. "RMC, elbows,
couplings, and fittings shall be permitted to be installed in concrete,
in direct contact with the earth, or in areas subject to severe corrosive
influences where protected by corrosion protection and judged suitable
for the condition."
IMC
Section 342.10 (B) Corrosion Environments. "IMC, elbows, couplings,
and fittings shall be permitted to be installed in concrete, in direct
contact with the earth, or in areas subject to severe corrosive influences
where protected by corrosion protection and judged suitable for the
condition."
EMT Section 358.10 (B) Corrosion Protection. "Ferrous or
nonferrous EMT, elbows, couplings, and fittings shall be permitted
to be installed in concrete, in direct contact with the earth, or
in areas subject to severe corrosive influences where protected by
corrosion protection and judged suitable for the condition."
RSC,
IMC and EMT are all "protected by corrosion protection" due to the
zinc coating that is applied during the manufacturing process. However,
in severe corrosive environments, the designer or AHJ may decide
to require additional or supplementary protection.
Underwriters
Laboratories' Electrical Construction Equipment Directory contains
information relating to limitations or special conditions applying
to products listed by UL. The Directory states that RSC and IMC do
not generally require supplementary corrosion protection when installed
in soil unless: 1. Soil resistivity is less than 2000 ohm-centimeters.
2. Local experience has confirmed that the soil is extremely corrosive.
(Note:
Soils producing severe corrosive effects have low electrical resistivity,
expressed in ohm-centimeters. Local electric utilities commonly measure
the resistivity of soils. The authority having jurisdiction (AHJ)
has the authority to determine the necessity for additional protection.)
EMT
in direct contact with the soil generally requires supplementary
corrosion protection. However, local experience in some areas of
the country has shown this to be unnecessary.
Back to Questions
|
5.The National Electrical Code® considers all underground installations a "wet location".
2005 NEC®, Article 100 defines a wet location as follows:
Wet Location. Installations underground or in concrete slabs or masonry in direct contact with the earth, and locations subject to saturation with water or other liquids, such as vehicle washing areas, and locations exposed to weather and unprotected.
No raceway system is really "watertight", including those that are glued or have sealed joints. Normally raceways will collect condensation. The raceway is designed to allow this moisture to drain out. It is understandable that in some cases where the ground does not percolate well, the water will also seep in. This is why the conductors installed must be of a type approved for wet locations i.e. THWN or XHHW.
If the presence of water is a problem, one of the following steps may help: 1. Install a typical Quazite(TM) concrete-polymer underground open bottom junction box over a gravel sump. This can be done by excavating a hole approximately 3' X 3; filling it with 1 to 2 inch gravel and placing the Quazite(TM) box flush with the ground prior to entering the building, or at the lowest location in the conduit run. 2. Install type ECDB or equivalent drain fittings to permit the water to drain out of the conduit. These would normally be installed in all above the ground locations prior to entering each building or piece of equipment.
The 2005 NEC® permits EMT, IMC and RMC to be installed in all wet locations both inside and outside. NEC® 300.6(C) requires all metallic raceways installed indoors in a wet location to be mounted so there is at least a 1/4" inch air space between the raceway and the supporting surface to minimize the accumulation of moisture. NEC® Sectons 342 (345).10(D), 344 (346).10(D) and 358 (348).10(C) caution the installer that all hardware items such as straps, bolts, screws etc. be of a corrosion resistant material when used to support raceways in wet locations. When threadless fittings are used with RMC and IMC, they must be identified and listed for the application. Threadless fittings intended for use in wet locations are marked "Raintight" or "Wet locations" on the fitting or its smallest unit shipping container. Threadless fittings intended for embedment in poured concrete are marked "Concrete-tight" or "Concrete-tight when taped" or "Raintight" on the fittings' smallest unit shipping container. Fittings listed as "raintight" are also "Concrete-tight", but not all concrete-tight fittings are raintight. For more information, see Section 4.3, Fittings For Use With RMC, IMC, and EMT in the publication Guidelines for Installing Steel Conduit/Tubing.
Back to Questions |
|
6. The National Electrical Code (NEC)
allows all three products to be installed in concrete, as noted in
their respective Articles: (Also see NEC 300.6(A)(3).
RMC Section 344.10 (B) Corrosion
Environments. "RMC, elbows, couplings, and fittings shall
be permitted to be installed in concrete, in direct contact
with the earth, or in areas subject to severe corrosive influences
where protected by corrosion protection and judged suitable for the
condition."
IMC Section 342.10 (B) Corrosion
Environments. "IMC, elbows, couplings, and fittings shall
be permitted to be installed in concrete, in direct contact
with the earth, or in areas subject to severe corrosive influences
where protected by corrosion protection and judged suitable for the
condition."
EMT Section 358.10 (B) Corrosion
Protection. "Ferrous or nonferrous EMT, elbows, couplings,
and fittings shall be permitted to be installed in concrete,
in direct contact with the earth, or in areas subject to severe corrosive
influences where protected by corrosion protection and judged suitable
for the condition."
Rigid steel conduit, IMC and EMT are
all "protected by corrosion protection" due to the
zinc coating that is applied during the manufacturing process. However,
in severely corrosive environments, the designer or AHJ may decide
to require additional or supplementary protection. If supplementary
corrosion protection is required or desired, it can be provided by
a factory-applied PVC coating, a paint approved for the purpose,
or tape wraps approved for the application
When steel conduit/EMT emerge from
concrete into soil, we recommend that supplementary corrosion protection
be applied a minimum of 4 inches on each side of the point where
the conduit or EMT emerges. This LINK
will take you to an individual page from the STI Installation Guide
pertaining to concrete installation.
Underwriters Laboratories' Electrical
Construction Equipment Directory contains information relating
to limitations or special conditions applying to products listed
by UL.
The UL Directory states that supplementary
corrosion protection is not required on rigid steel conduit
and IMC when installed in concrete.
The UL Directory states the following
for EMT: "Galvanized steel electrical metallic tubing installed
in concrete on grade or above generally requires no supplementary
corrosion protection. Galvanized steel electrical metallic tubing
in concrete slab below grade level may require supplementary corrosion
protection."
Where the concrete slab is installed
on grade, it is important that the raceway be placed in between layers
of rebar and above the bottom of the slab to insure full encasement.
However, there are structural concerns that must be satisfied. These
concerns are related to size of the conduit or tubing to be encased
and the thickness of the slab.
The International Building Code (IBC)
contains information in section 1906.3 concerning conduits and pipes
embedded in concrete. According to the IBC Handbook, "Conduits,
pipes and sleeves may be embedded in concrete, provided that the
properties of the material or the size and location of embedments
will not damage the concrete." (Aluminum conduit cannot
be embedded in concrete unless provided with supplementary corrosion
protection.) The IBC references ACI (American Concrete Institute)
318, Section 6.3 which provides guidance for safe installations under
common conditions.
The Authority having Jurisdiction
responsible for the structural integrity of the installation should
also be consulted.
Back to Questions
|
|
7. The
requirements in NFPA 130, Section 5.4 Wiring Requirements state that "Materials manufactured for use as conduits, raceways, ducts,
boxes, cabinets, equipment enclosures, and their surface finish materials
shall be capable of being subjected to temperatures up to 500°C
(932°F) for 1 hour and shall not support combustion under the
same temperature condition."
Steel
conduit is zinc-galvanized for corrosion protection. Underwriters
Laboratories exposed rigid steel conduit and steel intermediate metal
conduit and electrical metallic tubing to a 4 hour ASTM E119 fire
test at a temperature of 2000°F. The conduit and EMT were still
intact at the end of the test. This information is contained in a
report Annular Space Protection of Openings Created by Penetrations
of Tubular Steel Conduit a Review of UL Special Services Investigation
File NC546 Project 90NK111650, which is available from Allied
Tube.
Since
the melting point of zinc is around 800°F, the galvanizing may
be compromised but the conduit and EMT would still be intact after
the E119 fire and would not be "capable of supporting combustion".
We cannot verify the condition of the conductors within the conduit.
However, Fire-resistive Circuit integrity cables can be used within
conduit to obtain a 2-hour fire rating,.
Back to Questions
|
|
8. The
coefficient of expansion for steel conduit/EMT is 6.5x10-6 in./in./°F. This is significant as it relates to whether or not
expansion fittings would be required in a particular application.
Expansion fittings are installed where significant temperature differentials
are anticipated. These temperature shifts cause materials to expand
and contract and could result in the conduit being pulled apart at
the joint. Expansion fittings are not normally required with steel
conduit/tubing because their coefficient of expansion is identical
to or similar to that of other common building materials. However,
when steel conduit is installed on bridges or rooftops or as an outdoor
raceway span between buildings, expansion fittings may be required.
In these types of installations, there is a probability that expansion
and contraction would occur, resulting from the direct heat of the
sun coupled with significant temperature drops at night. Expansion
characteristics of steel conduit/tubing are shown in Table 3,
at 5°F to 200°F in 5°F increments. The Table also shows
the length changes for steel conduit at each temperature differential.
This will help determine the need for expansion fittings. For information
about the use of expansion fittings, contact your fittings supplier.
Back to Questions
|
|
9. The
Trade Sizes and Metric Designator equivalents for RSC, IMC, and EMT
are:
|
Trade
Size
1/2
3/4
1
1 1/4
1 1/2
2
2 1/2
3
3 1/2
4
5
6
|
Metric
Designator
16
21
27
35
41
53
63
78
91
103
129
155
|
Note: The Trade
Sizes and Metric Designators are for identification purposes only
and are not actual dimensions. Product dimensions do not change.
Back to Questions
|
|
10. No
fire-rating is required since these products are defined as noncombustible
by the building codes. This question is usually asked relative to
the penetration of a fire-rated assembly or use in an emergency circuit,
fire pump, or mass transit vehicle (see Question 4 for information
on NFPA 130 "Standard for Fixed Guideway Transit and Passenger Rail
Systems").
1.Penetrations
The NEC® and building codes require the sealing of openings around
raceways that penetrate a fire-rated assembly. This requirement is
to prevent smoke, gases and flames from migrating from one area to
another. There are many listed penetration firestopping systems that
can be used to seal openings; the listing instructions should be
strictly followed.
Most building codes permit the openings around galvanized steel RSC,
IMC and EMT in concrete or masonry to be filled with cement, mortar,
or grout. However, since local codes sometimes vary, these requirements
should be checked prior to installation.
2.Emergency
circuits
Prior to installing these circuits, the NEC® and local or state
code requirements should be reviewed. Steel raceways withstand fire
(see Question 4); however, ordinary conductor insulation melts when
exposed to elevated temperatures and a short circuit can be created.
This is the reason for special protection of emergency and fire-pump
circuits.
Methods of thermal protection include enclosing the raceways in a
fire-rated enclosure, embedding them in concrete, wrapping them with
a listed wrap system for protection from fire (sometimes called Electrical
Circuit Protection System or Thermal Barrier Protection for Electrical
components), and using conductors specifically rated to maintain
the circuit.
The
NEC does not require these thermal protection methods where conduit
is installed in a fully sprinklered building.
Back to Questions
|
|
11. Yes,
according to Section 230.28 of the 2005 NEC¨ the only requirement
is that the service mast "...shall be of adequate strength or be
supported by braces or guys to withstand safely the strain imposed
by the service drop."
|
|
12. Yes,
even though IMC is lighter and has a thinner wall thickness than
rigid, it is just as strong. This is achieved through the steel processing
during manufacturing. NEC®
Articles 342 (formerly article 345) for Intermediate Metal Conduit
and 344 (formerly article 346) for Rigid Metal Conduit contain identical
installation requirements. Both products are UL listed and have been
tested under similar conditions.
|
|
13. Cutting
and threading of IMC is covered extensively in the Steel Tube Institute
publication Guidelines
for Installing Steel Conduit/Tubing under Section
4, General Installation Practices. You can jump to that section by
clicking here
to download a pdf file.
|
|
14. The
NEC requires that the threads of both RSC and IMC be cut with a 3/4
inch taper per foot (1 in 16) per ANSI/ASME B.1.20.1 Standards
for Pipe Threads, General Purpose (Inch). This applies to both
factory and field threads. This is the same taper as standard plumbing
pipe.
Back to Questions
|
|
15. Factory
cut threads have corrosion protection applied at the factory. Field
cut threads are required to be coated "with an approved electrically
conductive, corrosion-resistant compound "where corrosion protection
is necessary " (see NEC®
2005 300.6 (A). We recommend that all field cut threads be protected
against corrosion where they will be installed in wet or outdoor
locations. The thread surface should be protected with conductive
rust resistant coating. Zinc-rich paint is a typical coating, but
there are other conductive coatings that can be used.
Field
threads should be cut one thread short. This will insure a good connection
and allow the entire thread surface to be inside the coupling.
Back to Questions
|
|
16. The
Rigid Steel Conduit used in the U.S. is manufactured to UL Safety
Standard No. 6 and to ANSI C80.1. There is one IEC standard entitled
Extra Heavy-Duty Rigid Conduit (IEC 981) which is very similar
to the Rigid Steel Conduit listed to UL 6 with the exception of some
dimensional differences. At the current time, no one lists product
to IEC 981.
|
|
17. The
term "schedule 40" originated when ASTM A120 existed and conduit
was made from this pipe. A120 was cancelled many years ago. Steel
conduit is not required to meet ASTM standards. For any future information,
contact steel conduit manufacturers.
Back to Questions
|
|
18. Underwriters
Laboratories Electrical Construction Equipment Directory states that EMT is listed for "installation of conductors in circuits
rated above or below 600V, nominal, and in accordance with a ANSI/NFPA
70, National Electrical Code".
Part
II of Article 300 (Wiring Methods) of the National Electrical Code® covers "Requirements for Over 600 Volts, Nominal". In Section 300.37
of Part II entitled "Aboveground Wiring Methods", EMT is listed as
one of the permitted wiring methods.
In
1996 Underwriters Laboratories published a report of research entitled
Electrical Metallic Tubing for use over 600 Volts. To view a copy
of the report, click here.
Back to Questions
|
|
19. Yes,
RSC, IMC and EMT are all permitted as an equipment grounding conductor
in accordance with NEC®
250.118. It is permitted to add a supplementary equipment grounding
conductor sized in accordance with NEC®
250.122. This is a systems design consideration. If a supplementary
equipment grounding conductor is used, it is still very important
to comply with NEC®
300.10 and 300.12, since approximately 90% to 95% of the current
will flow on the conduit and not in a supplementary conductor. For
information on the equipment grounding capabilities of RSC, IMC and
EMT, click here
for a link to the section with the results of a research study performed
by the Georgia Institute of Technology.
Back to Questions
|
|
20. Yes.
A copy of the study
conducted by Georgia Institute of Technology titled Modeling and
Evaluation of Conduit Systems for Harmonics and Electromagnetic Fields
is the basis for the Grounding and ElectroMagnetic Interference (GEMI)
Analysis software,
which is available for downloading.
Back to Questions
|
|
21. Steel
conduit and tubing offers several advantages over alternative wiring
methods:
EMI Shielding
Physical protection of conductors
Proven grounding capabilities
Low coefficient of expansion - infrequent need for expansion
fittings
Impact resistant -high tensile strength
Noncombustible
Adaptable to future wiring changes
Low life-cycle costs
Recyclable (For more documentation click HERE)
|
|
22. There
is no prohibition in the NEC®. In some installations, there may
be a concern about physical damage or corrosion protection. This
is often a judgment call by the authority having jurisdiction. The
NEC® does not allow EMT to be used where "during installation
or afterward, it will be subject to severe physical damage". The
NEC® also requires the EMT to be "securely fastened in place"
and provides requirements for supports. The AHJ may determine more
supports are necessary. If the AHJ approves the installation with
EMT, consideration should be given to compliance with NEC® 110.12,
300.6, 300.7(A) & (B), 352.30 (formerly 348-13), 352.12 (1) (formerly
348.5(1) and 358.10 (C) (formerly 348.6).
|
|
23. Per
Article 358 in the 2002 NEC, all EMT associated fittings are required
to be listed for the installation (see 358.6). In 358.42, it is stated
that "Couplings and connectors used with EMT shall be made up tight.
Where buried in masonry or concrete, they shall be concretetight
type. Where installed in wet locations, they shall be of the raintight
type." The recently-published 2005 NEC contains a change in language
in 358.42 which now states: "Couplings and connectors used with EMT
shall be made up tight. Where buried in masonry or concrete, they
shall be concretetight type. Where installed in wet locations, they
shall comply with 314.15(A)." Article 314 includes installation requirements
for fittings used to join raceways and to connect raceways and cables
to boxes and conduit bodies. 314.15A states that in damp or wet locations,
boxes, conduit bodies, and fittings "shall be placed or equipped
so as to prevent moisture from entering or accumulating within the
box, conduit body, or fitting. Boxes, conduit bodies and fittings
installed in wet locations shall be listed for use in wet locations."
Select
this link to view UL Bulletin that includes additional information
on raintight fittings.
Raintight compression type EMT fittings for use in wet locations
Back to Questions
|
|
24. Unlike
other materials, steel contains recycled material and is also fully
recyclable. In fact, according to the Steel Recycling Institute (SRI),
steel is the world's most recycled material. All of the STINA conduit
producers use recycled steel in their conduit and tubing products.
Our members produce steel Electrical Metallic Tubing, Intermediate
Metal Conduit, and Galvanized Rigid Conduit.
The
amount of recycled material in steel conduit/tubing products depends
upon the process used by our various steel suppliers. If the pipe
is made from a steel coil that comes from a steel mini-mill, then
the scrap or recycled content of the steel is between 95-100% because
mini-mills use a technology called "electric arc furnace" (EAF) that
allows them to use up to 100% scrap. If the pipe is made from a steel
coil that comes from an integrated mill, then the scrap or recycled
content of the steel is about 30% because integrated mills use a
technology called "basic oxygen furnace" (BOF) that restricts the
use of scrap steel to no more than 30%. It is important to note that
economic expansion, domestically and internationally, creates additional
demand that cannot be fully met by available scrap supplies.
Both
the EAF and the BOF methods provide an enhanced environmental benefit.
One is not environmentally superior to the other, since they are
both complementary parts of the total interlocking infrastructure
of steelmaking, product manufacture, scrap generation and recycling,
as explained on the Steel Recycling Institute's website.
The
US Green Building Council has told us that CSI 15 (Mechanical) and
CSI 16 (Electrical) products are excluded from LEED points. Since
steel conduit is an electrical product, it, too, is omitted. We understand,
however, that our products exceed the 5% and 10% goals in LEED Version
2.1, Credits 4.1 and 4.2, regardless of which type of steel is used
in the manufacturing of the product.
The
additional "green" aspect of steel conduit is what the Steel Recycling
Institute terms the "reclamation rate". Currently LEED only considers
the recycled content of a product, not how much can be reclaimed
at the end of the service life or from jobsite scrap. Steel conduit
is exceptional relative to "reclamation rate." Four major factors
account for this:
- The service
life is very long. (There is steel rigid conduit still in use after
more that sixty years.)
- Conductors
can be removed and new conductors installed.
- Additional
circuits can frequently be added in the same conduit.
- When the
conduit is finally discarded, it is virtually totally recyclable.
You
may want to review two articles by the Steel Recycling Institute
(www.recycle-steel.org).
The two segments are "Steel Takes LEED with Recycled Content" and
"Modern Steel Production Technologies".
For more documentation click HERE.
Back to Questions
|
|
25. If
you have other questions or need additional information regarding
steel conduit, its uses, benefits or installation, please contact
Richard Loyd. Email: dickonel@aol.com Fax: 480-802-8125
Or,
go to the Producers Section under Technical
Contacts.
Back to Questions
|
|